Wenzhou Kinee Electrical Co., Ltd. is one of the most reliable manufacturers and suppliers of 40ka ac surge protection device in China. We warmly welcome you to wholesale 40ka ac surge protection device for sale here from our factory. All customized products are with high quality and competitive price.
Product Introduction
KNLY3-40 Series Surge Protective Device (SPD), also known as a lightning protector or surge arrester, is a 40kA AC Surge Protection Device used to protect electronic equipment, instruments, and low-voltage electrical circuits from damage caused by transient overvoltages (surges). When a sudden spike in current or voltage occurs in an electrical circuit or communication line due to external interference (such as lightning strikes, power grid operations, etc.), the SPD can conduct and divert the current within an extremely short time. In low-voltage AC electrical circuits, the 40kA AC Surge Protection Device limits the overvoltage to a safe range that the equipment can withstand. By diverting surge current, the 40kA AC Surge Protection Device helps prevent surge damage to other equipment in the circuit. The KNLY3-40 Series combines these protective functions in a 40kA AC Surge Protection Device.

Features
· Safe ultra-wide electrical clearance and creepage distance, ultra-high voltage withstand rating, meeting the usage requirements of high-altitude areas;
· No need to consider load current; plug-in design allows for hot-swapping (replacement while powered) and easy maintenance;
· Built-in thermal cut-off technology for high safety performance and no follow current;
· If any indicator window turns red, it indicates a fault and prompts replacement-clear and easy to identify;
· Optional remote signaling monitoring interface for remote monitoring;
· High operating voltage, high flow capacity, high safety performance, and high stability.
Technical parameters
|
Product model |
KNLY3-10 |
KNLY3-20 |
KNLY3-40 |
KNLY3-60 |
KNLY3-80 |
|
Rated voltage Un (V) |
275V/385V |
||||
|
Maximum continuous operating voltage Uc |
385V/420V/440V |
||||
|
Voltage protection level Up |
≤ 1.0kV |
≤ 1.2kV |
≤ 1.8kV |
≤ 2.0kV |
≤ 2.2kV |
|
Rated discharge current In (8/20μs) |
5kA |
10kA |
20kA |
30kA |
40kA |
|
Maximum discharge current Imax (8/20μs) |
10kA |
20kA |
40kA |
60kA |
80kA |
|
Response time tA (ns) |
≤ 25ns |
||||
|
Housing Material |
FR Reinforced Nylon (UL94V-0) |
||||
|
Recommended cross-sectional area |
16-35mm² |
||||
|
Protection rating |
IP20 |
||||
|
Installation method |
35mm DIN rail |
||||
|
Operating temperature |
-40°C ~+80°C |
||||