Double-break Transfer Switch

Double-break Transfer Switch
Details
1.Automatic Transfer Switch: with "priority" phase
2.Microcontroller-based.
3.Digital display of working voltage, current.
4.Measurement accuracy is 0.5 class.
5.Key setting parameter.
6.Can set the priority phase sequence.
7.DIN rail mounting.
Category
Intelligent Power Transfer Switch
Send Inquiry
Add To Inquiry
Share to
Description

Wenzhou Kinee Electrical Co., Ltd. is one of the most reliable manufacturers and suppliers of double-break transfer switch in China. We warmly welcome you to wholesale double-break transfer switch for sale here from our factory. All customized products are with high quality and competitive price.

 

Product Introduction

 

Double-break transfer switch is a microcontroller-based automatic transfer switch with dual power supply (L1/L2) automatic switching capability and support for priority phase selection. It features a digital display of operating voltage and current, with a measurement accuracy of Class 0.5. Users can set various parameters via buttons to achieve power-on delay, switching delay, timed on/off, over-voltage protection (adjustable from 120V to 300V), under-voltage protection (adjustable from 80V to 210V or OFF), over-current protection (adjustable from 1A to 63A/100A, including action delay and continuous trip count limit), and temperature protection (adjustable from 40°C to 120°C). The product is designed for DIN rail mounting and is suitable for power distribution applications requiring intelligent power management and safety protection.

product-1460-636

 

Technical Parameters

 

Parameter

Value

Rated supply voltage

AC 2×110V/220V

Operating voltage range

AC 80-300V

Rated frequency

50/60Hz

Hysteresis

Overvoltage: 5V
Undervoltage: 5V

Measurement accuracy

Class 0.5

Rated insulation voltage

450V

Output contact

1NO

Electrical life

10⁸

Mechanical life

10⁶

Protection class

IP20

Pollution degree

3

Altitude

<2000m

Operating temperature

-5°C ~ 40°C

Humidity

≤50% or 40°C

Storage temperature

-10°C ~ 55°C

 

Program Description

 

Set character

Technical parameter

Set range

Default value

Step forward

Function description

P-1

Power-on delay time

1S-999S

5S

1S

After external power cut, the time needed for power-on when power recovery.

P-2

Recovery/Switch Time

1S-999S

10S

1S

Is the time required for the line to return to normal or switch to a working line.

P-3

Timed off

OFF-0.1m-999m

OFF

0.1m

Can be used to timed off the device.

P-4

Timed on

ON-0.1m-999m

ON

0.1m

The P-3 timer off parameters must be changed before the timer on parameters can be adjusted.

P-5

Input phase priority selection

L1-L2-ATO

L1

1

Operating mode: When L1 or L2 is selected, it's a priority phase selection; ATO: Non-priority mode, fixed to the current phase.

P-6

Over-voltage protection value

120V-300V -OFF

270V 140V

1V

When the voltage of one phase is over the set value, the protector will cut off this phase and switch to the next phase according to the sequence set in P5. When all voltage is over the set value, the protector will cut off all lines.

P-7

Under-voltage protection value

OFF-80V-210V

170V 90V

1V

When the voltage of one phase is under the set value, the protector will cut off this phase and switch to the next phase according to the sequence set in P5. When all voltage is under the set value, the protector will cut off all lines.

P-8

Voltage calibration

±9.9%

0

0.1%

Correct the voltage error.

P-9

Over-current protection value

1A-63A/100A -OFF

63A 80A

1A

When the current is higher than the set value, the protector will cut off the line. When setting OFF, the protector will turn off over-current protection function.

P-10

Current calibration

±9.9%

0

0.1%

Calibrate current current value.

P-11

Overcurrent protection action time

0.1S-30S

1S

0.1s

When over current, the time needed for protection action.

P-12

Times of continuous over current protection

OFF-1-20

OFF

1

When the times of continuous over-current protection exceeds the set value, the protector will cut off the line, then it needs to be opened manually.

P-13

Temperature protection

40°C-120°C

90°C

1°C

After temperature protection, the hysteresis value is restored to 10°C.

 

Questions and Answers

 

Q: When can I expect to receive a quote and detailed information after submitting an inquiry?

A: A reply will be sent within 24 hours.

Q: What makes you different from other suppliers?

A: We have a full range of electrical products and can also customize products to meet your specific needs.

Q: Do you provide samples? Are they free or extra?

A: Yes, we can provide samples free of charge, but we will not cover the shipping costs.

Q: Can I get a sample for testing before placing an order?

A: Of course!

Q: How's the delivery? I really need them urgently!

A: Samples require 5-7 days. Bulk orders require 12-15 days.

 

Hot Tags: double-break transfer switch, China double-break transfer switch manufacturers, suppliers, factory, Automatic Transfer Switch 3 Way 4 Way, Double break Transfer Switch, intelligent power transfer switch

Send Inquiry