Electrical AC Contactor All-copper Coil

Electrical AC Contactor All-copper Coil
Details
Model:KNX2 series
Rated operating current: 9-95A
Rated operating voltage: 220V~690V
Rated insulation voltage: 690V
Standards: IEC 60947-1, IEC 60947-4-1
Category
Contactor
Send Inquiry
Add To Inquiry
Share to
Description

Wenzhou Kinee Electrical Co., Ltd. is one of the most reliable manufacturers and suppliers of electrical ac contactor all-copper coil in China. We warmly welcome you to wholesale electrical ac contactor all-copper coil for sale here from our factory. All customized products are with high quality and competitive price.

 

Product Introduction

 

The KINEE KNX2 series Electrical AC Contactor All-copper coil AC contactors feature a novel appearance and compact structure. They are primarily used for frequent starting and controlling of AC motors, remote connection and disconnection of circuits, and can be combined with appropriate thermal overload relays, along with Electrical AC Contactor All-copper coil, to form electromagnetic starters.


The Electrical AC Contactor All-copper coil ensures reliable operation and long service life. Compliant with standards: IEC 60947-1, IEC 60947-4-1, Electrical AC Contactor All-copper coil.

product-1460-681

 

Technical Parameters

 

Item

KNX2-09(Z)

KNX2-12(Z)

KNX2-18(Z)

KNX2-25(Z)

KNX2-32(Z)

Frame gradea

09~12

18

25

32

Rated Impulse Withstand Voltage Uimp (kV)

8

Rated Duty

Eight-hour workday, continuous workday, short-time workday, intermittent workday (load factor 40%)

Rated Limited Short-Circuit Current Iq (kA)

50 (400V)

Arcing Distance(mm)

10

Limiting Impedance(Ω)

0.05

Matching Fuse Type

gG20

gG32

gG40

gG50

Matching Fuse Rated Current(A)

20

32

40

50

Coordination Type

Type "2" coordination

Matching thermal overload relay model

NR2-25

NR2-25,36

Auxiliary circuit parameters

Ith(A)

10

AC-15

Ue/Ie:AC380V/400V/0.95A

DC-13

Ue/Ie: DC220V/250V/0.15A

Uimp(kV)

6

The type of fuse used in the auxiliary circuit

gG10

AC coil

50Hz

Pick-up (VA)

≤70

≤70

≤70

≤110

≤110

Hold(VA)

≤9

≤9

≤9.5

≤14

≤14

 

Power(W)

1.8~2.7

1.8~2.7

3~4

3~4

3~4

DC coil

 

Power(W)

≤9

≤9

≤11

≤11

≤11

Control loop Uimp(kV)

6

Range of motion

Pull-in voltage: (85%~110%) Us; Release voltage: AC (20%~75%) Us, DC (10%~75%) Us

 

Item

KNX2-40(Z)

KNX2-50(Z)

KNX2-65(Z)

KNX2-80(Z)

KNX2-95(Z)

Frame gradea

40~65

80~95

Rated Impulse Withstand Voltage Uimp (kV)

8

Rated Duty

Eight-hour workday, continuous workday, short-time workday, intermittent workday (load factor 40%)

Rated Limited Short-Circuit Current Iq (kA)

50 (400V)

Arcing Distance(mm)

12

Limiting Impedance(Ω)

0.05

Matching Fuse Type

gG63

gG80

gG125

Matching Fuse Rated Current(A)

63

80

125

Coordination Type

Type "2" coordination

Matching thermal overload relay model

NR2-93

Auxiliary circuit parameters

Ith(A)

10

AC-15

Ue/Ie:AC380V/400V/0.95A

DC-13

Ue/Ie: DC220V/250V/0.15A

Uimp(kV)

6

The type of fuse used in the auxiliary circuit

gG10

AC coil

50Hz

Pick-up (VA)

≤300

≤300

≤300

≤300

≤300

Hold(VA)

≤45

≤45

≤45

≤57

≤57

 

Power(W)

6~10

6~10

6~10

6~10

6~10

DC coil

 

Power(W)

≤22

≤22

≤22

≤22

≤22

Control loop Uimp(kV)

6

Range of motion

Pull-in voltage: (85%~110%) Us; Release voltage: AC (20%~75%) Us, DC (10%~75%) Us

 

"a" Contactors of the same frame class refer to contactors with the same external dimensions and internal structure, with only some differences in dimensions, but different rated operating currents; for example, KNX2-40 and KNX2-65 are contactors of the same frame class (40~65).

 

Hot Tags: electrical ac contactor all-copper coil, China electrical ac contactor all-copper coil manufacturers, suppliers, factory, contactor, High Performance AC Contactors

Send Inquiry