DC Types Of Mcb in Electrical

DC Types Of Mcb in Electrical
Details
Model: KNS3D-63F7A
Rated Voltage (V): 250V (1P), 500V (2P),750V (3P),1000V (4P),
Rated Current (A): 1A, 2A, 3A; 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A;
Number of Poles: 1P, 2P, 3P, 4P;
Rated short-circuit breaking capacity (kA): 6kA;
Instantaneous disconnector type and disconnect current:8-12In: 8-12In
Maximum cross-sectional area of connecting wire (25mm²): 25
Category
DC MCB
Send Inquiry
Add To Inquiry
Share to
Description

Wenzhou Kinee Electrical Co., Ltd. is one of the most reliable manufacturers and suppliers of dc types of mcb in electrical in China. We warmly welcome you to wholesale dc types of mcb in electrical for sale here from our factory. All customized products are with high quality and competitive price.

 

Product Introduction

 

The DC types of mcb in electrical series miniature DC circuit breakers are suitable for overload and short-circuit protection of lines, lighting, and power equipment in DC circuits with a maximum rated voltage of 1000V and a rated current of 63A and below. They can also be used for infrequent switching of lines and equipment under normal conditions.

product-800-387

 

Technical Parameters

 

Product Model

KNS3D-63F7A

Meets standards

IEC60947-2

Rated voltage (V)

250V(1P),500V(2P),750V(3P),1000V(4P)

Rated current (A)

1A,2A,3A;4A,6A,10A,16A,20A,25A,32A,40A,50A,63A

Extreme number

1P,2P,3P,4P

Rated short-circuit breaking capacity (kA)

6A

Instantaneous disconnector type and disconnect current

8-12In

Maximum cross-sectional area of ​​connecting wire (25mm²)

25

Electromechanical lifespan (times)

10000

 

Overcurrent Time-Operating Characteristics

 

Test

Test current

initial state

Time limit for disengagement or non-disengagement

Expected results

Test ambient temperature

a

1.05In

cold state

t ≤1h(In≤63A)

Non-dismounting

30°C~35°C

b

1.3In

Following test a

t<1h(In≤63A)

Snap

30°C~35°C

c

8In

cold state

t≤0.2s

Non-dismounting

30°C~35°C

d

12In

cold state

t<0.2s

Snap

30°C~35°C

 

The wiring is suitable for copper wires of 25mm² or less (see table below). The wiring method is to tighten the wires with screws with a torque of 2.0 N·m.

Rated current In (A)

Nominal cross-sectional area of ​​copper conductor (mm²)

1~6

1

10

1.5

16,20

2.5

25

4

32

6

40,50

10

63

16

 

Working Conditions

 

Temperature

The ambient air temperature should not exceed +40℃, should not be lower than -5℃,
and should not exceed +30℃ over 24 hours.

High

The altitude of the installation site should not exceed 2000m; if higher altitudes are required, derating should be performed according to IEC 61439 Technical Requirements for Low-Voltage Electrical Appliances for High-Altitude Use under Special Environmental Conditions.

Atmospheric conditions

At +40℃, the relative humidity should not exceed 50%, and higher relative humidity is permissible at lower temperatures; at an ambient air temperature of 55℃, the relative humidity should be ≤95%.

Resistance to damp heat

The average minimum temperature of the wettest month shall not exceed +25°C, and the average maximum relative humidity of that month shall not exceed 90%, taking into account condensation on the product surface caused by temperature changes.

Pollution level

Level 2

Installation Category

Ⅱ,Ⅲ

Installation method

Installed using TH35-7.5 type mounting rail.

Installation conditions

The inclination of the mounting surface from the vertical plane should not exceed 5°.

If condensation occurs on the product due to temperature changes, measures must be taken.

 

Video

 

 

Appearance And Installation Method

 

product-1305-350

product-420-401

 

Questions and Answers

 

Q: Can MCB be used as a switch?

A: MCB can function as an ON-OFF switch, allowing manual control of the circuit. However, it is important to note that an MCB should not be used as a frequent switching device, as its primary purpose is to protect the circuit from over currents rather than serve as a general-purpose switch.

Q: Can EA63s MCB be reset after tripping?

A: Yes, most MCB are designed to be manually reset after tripping. Once the fault or over current condition has been resolved, the MCB can be switched back to the ON position to restore power to the circuit.

Q: What is the difference between an EA63s MCB and a fuse?

A: EA63s MCB and a fuse both serve the purpose of protecting electrical circuits from over currents. However, the main difference is that an MCB can be manually reset after tripping, while a fuse requires replacement once it blows. EA63s MCB offer convenience and cost-effectiveness in the long run compared to fuses.

 

Hot Tags: dc types of mcb in electrical, China dc types of mcb in electrical manufacturers, suppliers, factory, dc mcb, High Stability Circuit Breaker, High Voltage Miniature Circuit Breaker, Maximum 1000V Miniature DC Circuit Breaker, solar pv, Types Of Circuit Breaker Used in DC

Send Inquiry