6kA Breaking Capacity RCCB

6kA Breaking Capacity RCCB
Details
Model: KNID-100L
Ue: AC 230V~240(2P), AC 400V~415V(4P)
Uimp: 6kV
Im/IΔm: 1500A
Ui: 500V
Category
RCCB
Send Inquiry
Add To Inquiry
Share to
Description

Wenzhou Kinee Electrical Co., Ltd. is one of the most reliable manufacturers and suppliers of 6ka breaking capacity rccb in China. We warmly welcome you to wholesale 6ka breaking capacity rccb for sale here from our factory. All customized products are with high quality and competitive price.

 

Product Introduction

 

KINEE KNID-100L RCCB (Residual Current Circuit Breaker, also known as leakage circuit breaker or residual current device) is a key protective device in low-voltage distribution systems, designed to provide protection against electric shock and fire hazards caused by earth leakage currents. As a 6kA Breaking Capacity RCCB, it ensures reliable short-circuit withstand capability in demanding installations.

 

This series offers AC, A, S and B types, with rated current from 16A to 125A, available in 2P(1P+N) and 4P(3P+N) versions to meet both single-phase and three-phase applications. The 6kA Breaking Capacity RCCB design enhances system safety by limiting the let-through energy during fault conditions.

 

Selectable residual operating currents of 10mA, 30mA, 100mA, and 300mA ensure reliable protection for personnel safety and equipment security. With its 6kA Breaking Capacity RCCB performance, the KNID-100L is suitable for a wide range of industrial and commercial distribution boards.

 

For superior protection and durability, choose this 6kA Breaking Capacity RCCB to safeguard both people and property against earth leakage and short-circuit risks.

 

product-1166-682

 

The KNID-100L electromagnetic residual current operated switch has the following functions:
· Supplementary personal protection against direct contact (≤ 30 mA)
· Personal protection against indirect contact (≥ 100 mA)
· Protection against insulation faults in electrical equipment, such as prevention of electrical fires (300 mA)
·Top-in bottom-out or bottom-in top-out wiring configuration

 

Technical parameters

 

Main Characteristics

Residual current protection type

Electromagnetic type

Rated operational voltage (Ue)

2P

230~240 V

4P

400~415 V

Operating frequency

50 Hz

Rated insulation voltage (Ui)

500 V

Pollution degree

3

Rated impulse withstand voltage (Uimp)

6 kV

Rated making and breaking capacity (Im/IΔm)

1500 A

Surge current withstand without tripping (8/20 µs)

Type AC (non-selective)

250 A

Type AC (selective)

3 kA

 

Other Characteristics

Rated conditional short-circuit current (Inc/IΔc)

Used with iC65N/H/L

Same as the breaking capacity of the associated iC65

Used with fuse

10,000 A

Degree of protection

Device

IP20

Installed in distribution board

IP40
Insulation class II

Endurance (O-C)

Electrical endurance (AC1)

25~63 A

15,000 operating cycles

80~100 A

10,000 operating cycles

Mechanical endurance

 

20,000 operating cycles

Operating temperature

-25°C~+60°C

Storage temperature

-40°C~+85°C

 

Send Inquiry